For use in the Denver Water Service Area

Material Specification – 4
for
Double-Disc Gate Valves

1. General:

All valves supplied under this specification shall be designed and manufactured in accordance with AWWA C500, with the following additional requirements or exceptions.

2. Valve Description:

Valves shall be iron body, double disc gate valves, fully bronze mounted, with non-rising stem and parallel seats.

3. Installation:

Valves will be installed with the stem vertical in buried horizontal water lines without gearing, bypasses, rollers or tracks.

4. Service:

All valves shall be suitable for frequent operation as well as service involving long periods of inactivity. Valves shall be capable of operating satisfactorily with flows in either direction. The operating pressure for all sizes shall be 200 psig.

5. Valve Stems:

Valves shall be furnished with 2 inch square wrench nuts. The wrench nut shall comply with AWWA C500. Stem seal shall consist of O-rings in accordance with AWWA C500. The valves shall open by turning to the right.

6. Bolting Material:

Bonnet and gland bolts and nuts shall be either fabricated from a low alloy-steel for corrosion resistance or electro plated with zinc or cadmium. The hot dip process in accordance with ASTM A l53 is not acceptable.

7. End Connections:

A. Flanges:

Flanges shall be sized and drilled in accordance with ANSI B16.1 Class 125. Flanges shall be machined to a flat surface with serrated finish in accordance with AWWA C207.

B. Mechanical Joint:

All components of this type of joint shall conform to AWWA C111. The tee-head bolts and hexagon nuts shall be fabricated from a high-strength, low alloy steel known in the industry as Cor-Ten, Usalloy, or shall be ductile iron Durabolt.

Accessories for the mechanical joint consisting of the gasket, gland and fasteners shall be furnished and packaged separately from the valves. Each package shall be labeled in such a manner as to provide for proper identification and the number of units per package or bundle.

8. Testing:

Each valve, after shop assembly, shall be given the operation and hydrostatic tests in accordance with AWWA C500.

9. Coating:

All valves shall be painted or coated in accordance with AWWA C500. Machined flange faces shall not be painted or coated with the same coating as the body, but shall be shop coated with a rust preventive compound.

10. Certification:

The manufacturer shall furnish a sworn statement that the inspection and all the specified tests have been made and the results thereof comply with the requirements of the applicable standard(s) herein specified. A copy of the Certification including compliance with NSF/ANSI 61 shall be sent to Denver Water.

11. Acceptable Manufacturers:

Mueller
Clow