For use in the Denver Water Service Area |
Materials Specification – 27
for
Mechanical Joint Restraint
1. General:
All mechanical joint restraints shall be incorporated in the design of a follower gland. The gland shall be manufactured of ductile iron conforming to ASTM A 536. Dimensions of the gland shall be such that it can be used with the standardized mechanical joint bell and tee-head bolts conforming to AWWA C111 and C153.
2. Description:
The restraint mechanism shall consist of numerous individually activated gripping surfaces to maximize restraint capability. The gripping surfaces shall be wedges designed to spread the bearing surfaces on the pipe. Twist-off nuts, sized same as tee-head bolts, shall be used to insure proper actuating of restraining devices. When the nut is sheared off, a standard hex nut shall remain.
3. Pressure:
The mechanical joint restraint device for ductile iron pipe shall have a working pressure of at least 250 psi with a minimum safety factor of 2.
The mechanical joint restraint device for PVC shall have a working pressure of at least 150 psi with a minimum safety factor of 2:1.
4. Acceptable Manufacturers:
| For Ductile Iron Pipe: | |||
| Romal Rom Grip | (4" – 36") | ||
| EBAA Iron, Inc. | Megalug 1100 series | (4" - 36") | |
| Uni-Flange | Series 1400 | (4" – 36") | |
| Star Grip | Series 3000 | (4" – 36") | |
| Sigma – One Lok | (4" – 12") | ||
| For PVC Pipe: | |||
| EBAA Iron, Inc. | Megalug 2000 PV series | (4" - 12") | |
| Sigma One Lok | (4" - 12") | ||
| Star | |||
| For Bell – Spigot Device | |||
| Ductile Iron Pipe | |||
| Mega Lug | Series 1700 | ||
| U.S. Pipe Field Lok Gasket | |||
| PVC Pipe | |||
| Mega Lug | Series 1500 | ||
| For DI Pipe (Hydrants and Valves) | |||
| Mueller Aquagrip Restraint Device | |||