For use in the Denver Water Service Area |
Materials Specification – 1
for
Ductile Iron Pipe
Push-On Single Gasket Joint 3 Inch, 4 Inch, 6 Inch, 8 Inch, 12 Inch, 16 Inch, 20 Inch, 24 Inch, 30 Inch, 36 Inch, And 42 Inch Diameter
1. General:
All ductile iron pipe shall be manufactured in accordance with AWWA C151, with the following additional requirements or exceptions.
2. Size of Pipe:
This Specification shall cover ductile iron pipe in 3 inch, 4 inch, 6 inch, 8 inch, 12 inch, 16 inch, and 20 inch, 24 inch, 30 inch, 36 inch, and 42 inch nominal diameters.
3. Joint Type:
Push-on Single Gasket type conforming with applicable requirements of AWWA C111. Joint types other than Push-on Single Gasket are acceptable if specifically approved by Denver Water.
4. Pipe Wall Thickness:
Pipe furnished under this Specification shall have the following minimum ductile iron wall thickness:
| Nominal Pipe Diameter (Inches) | Minimum Ductile Iron Wall Thickness (Inches) | ||
|---|---|---|---|
| 3 | 0.25 | ||
| 4 | 0.26 | ||
| 6 | 0.25 | ||
| 8 | 0.27 | ||
| 12 | 0.31 | ||
| 16 | 0.34 | ||
| 20 | 0.36 | ||
| 24 | 0.41 | ||
| 30 | 0.43 | ||
| 36 | 0.48 | ||
| 42 | 0.53 | ||
5. Pipe Length:
Pipe furnished under this Specification shall have normal laying lengths of either 18 feet or 20 feet. Random lengths are not acceptable.
6. Material Strength:
The grade of iron shall be 60/42/10.
7. Cement-Mortar Lining:
Pipe furnished under this Specification shall have standard thickness cement-mortar linings in accordance with AWWA C104.
8. Certification:
The manufacturer shall furnish a sworn statement that the inspection and all of the specified tests have been made, and the results thereof comply with the requirements of the applicable Standard(s) herein specified. A copy of the Certification including compliance with NSF/ANSI 61 shall be sent to Denver Water.
9. Acceptable Manufacturers:
American Cast Iron Pipe
Griffin Pipe
Pacific States
U.S. Pipe